Summary
The following formulas were derived in the chapter on controllers:
Steady-state error
P controller on a plant with P behaviour: the controller gain is determined from the permissible control error.
\[
\begin{gathered}
\frac{e}{w} = \frac{1}{1 + A} \\[6pt]
A = k_{PR} \cdot k_{PS}
\end{gathered}
\]
I controller on a plant with P behaviour: no control error remains.
\[
\begin{gathered}
A = k_{IR} \cdot k_{PS} \cdot \frac{1}{s} \\[6pt]
H_{\mathrm{FÜ}} = \frac{1}{1 + \frac{1}{k_{IR} \cdot k_{PS}} \cdot s} = \frac{k_{P,\mathrm{FÜ}}}{1 + \tau_{\mathrm{FÜ}} \cdot s} \\[6pt]
k_{P,\mathrm{FÜ}} = 1 \text{ and } \tau_{\mathrm{FÜ}} = \frac{1}{k_{IR} \cdot k_{PS}} \\[6pt]
H_{\mathrm{FÜ}}(s = 0) = 1 \rightarrow \text{no steady-state control error}
\end{gathered}
\]
Transient response
P controller on a plant with I and PT1 behaviour:
\[
\begin{gathered}
k = k_{PR} \cdot k_{IS} \cdot k_{PS} \\[6pt]
\omega_0 = \sqrt{\frac{k}{\tau_S}} \rightarrow \omega_0 \sim \sqrt{k_{PR}} \\[6pt]
D = \frac{\omega_0}{2k} = \frac{1}{2} \sqrt{\frac{1}{k \cdot \tau_S}} \rightarrow D \sim \sqrt{\frac{1}{k_{PR}}}
\end{gathered}
\]
PID controller
\[
\begin{gathered}
H_R = \frac{u}{e} = k_{DR} \cdot s + k_{PR} + k_{IR} \cdot \frac{1}{s} \\[6pt]
H = \frac{u}{e} = k_{PR} \cdot \left(T_V \cdot s + 1 + \frac{1}{T_N} \cdot \frac{1}{s}\right) \\[6pt]
T_V = \frac{k_{DR}}{k_{PR}},\quad T_N = \frac{k_{PR}}{k_{IR}}
\end{gathered}
\]
Storage elements in the control loop
A storage element (integrator) in the control loop holds the output quantity when the control error is zero:
\[
y(t) = y_0 + \int e(t)\,dt \xrightarrow[e = 0]{} y_0
\]
Ziegler–Nichols method
KPR,Krit: minimum gain of a P controller for a stable sustained oscillation (critical gain), TKrit: period of this sustained oscillation (critical period).
| \(K_{PR}\) | \(K_{IR}\) | \(K_{DR}\) | |
|---|---|---|---|
| P controller | \(0.5 \cdot K_{PR,\mathrm{Krit}}\) | – | – |
| PI controller | \(0.45 \cdot K_{PR,\mathrm{Krit}}\) | \(0.53 \cdot \dfrac{K_{PR,\mathrm{Krit}}}{T_{\mathrm{Krit}}}\) | – |
| PID controller | \(0.6 \cdot K_{PR,\mathrm{Krit}}\) | \(1.2 \cdot \dfrac{K_{PR,\mathrm{Krit}}}{T_{\mathrm{Krit}}}\) | \(0.075 \cdot K_{PR,\mathrm{Krit}} \cdot T_{\mathrm{Krit}}\) |