Learning Content and Theses

Platform for digital learning at HSHL

Three-Phase Current

Reference system

Let us look at the time waveforms of a three-phase system at f = 50Hz or T = 20ms over three electrical periods. So far, only one electrical period has always been shown; I would like to break this pattern here:

Time waveforms of the three-phase currents i1, i2 and i3 over three periods from 0 to 60 ms

A three-phase system is symmetrical with respect to the phases. If we add the amplitudes of the three currents at any point in time, the result is always 0. The time t = 0s is a good choice for this. The blue waveform is at 0A; the green and red waveforms have the same amplitude with opposite signs. We can also verify this mathematically:

\[ \begin{gathered} i_1(\omega) = \hat{\imath} \\[4pt] i_2(\omega) = \hat{\imath}\left(-\frac{1}{2} - j\frac{\sqrt{3}}{2}\right) \\[4pt] i_3(\omega) = \hat{\imath}\left(-\frac{1}{2} + j\frac{\sqrt{3}}{2}\right) \\[6pt] i_1(\omega) + i_2(\omega) + i_3(\omega) = \hat{\imath} + \hat{\imath}\left(-\frac{1}{2} - j\frac{\sqrt{3}}{2}\right) + \hat{\imath}\left(-\frac{1}{2} + j\frac{\sqrt{3}}{2}\right) \\[4pt] = \hat{\imath}\left(1 - \frac{1}{2} - \frac{1}{2}\right) + j\hat{\imath}\left(-\frac{\sqrt{3}}{2} + \frac{\sqrt{3}}{2}\right) = 0 \end{gathered} \]

If the sum of the currents is always 0, this gives us freedom in the wiring. It is then possible, for example, to connect the currents in “star”.

Motor with three current sources and equivalent circuit: coil pairs L1/L4, L2/L5, L3/L6 in star with the currents i14, i25, i36

The 6 electromagnets are coils. From now on they are described with the circuit symbols for inductors from electrical engineering. In each case a current flows through two coils connected in series. The arrangement of the coils in a circle is of central importance for electrical machines. For their electrical control it does not matter. That is why I draw the series connection of current source and coils in the way that is simplest for electrical understanding.

At the lower terminal, current from an AC source is fed into the coils. At the upper node, the node rule applies:

\[ i_{14} + i_{25} + i_{36} = 0\,\mathrm{A} \]

With three-phase current, the node rule is always satisfied, because we found above that with three-phase current the sum of the three currents is 0A at every point in time anyway.

Caution: this applies only with a symmetrical load, see later chapter!

So we may combine the currents at one node without it affecting the amplitudes of the current. That is extremely convenient. At time t = 0s, the current i36 flows into the node. The current flows completely out of the node again as i25. The current i14 is 0A. At other times, the current divides differently at the node.

Three-phase voltage

You know AC voltage and you know three-phase current. The step to three-phase voltage is not far. Over time it follows the same phase-shifted waveform as three-phase current. The voltage at a socket is always 230VEff (RMS). The voltage in the “grid” (supply grid) is fixed; the current varies. At the socket in your home:

\[ \begin{gathered} u(t) = 325\,\mathrm{V} \cdot \sin(\omega t) \\[4pt] \text{with } \omega = 2\pi f \text{ and } f = 50\,\mathrm{Hz} \\[4pt] \hat{u} = 325\,\mathrm{V},\; u_{\mathrm{Eff}} = U = \frac{\hat{u}}{\sqrt{2}} = 230\,\mathrm{V} \end{gathered} \]

Colloquially, the RMS value of the voltage at the socket is given as U = 230V. From the fundamentals of electrical engineering you are used to working with peak values. Since the RMS value is better suited for power specifications than the peak value, drive technology and grid supply technology almost always work with the RMS value. For the theory, see also Peak value and RMS value.

In your home you probably also have a three-phase connection. The cooker with the oven is usually connected to it. These two are often the largest consumers of electrical power in your home. Three-phase voltage consists of three sources, each providing the socket voltage. The relationship between the three-phase voltage and the 230V socket voltage is as follows:

Three-phase grid with the line conductors L1, L2, L3 and the neutral conductor N, peak value phasors and RMS phasors
Spitzenwertzeiger = peak phasor · Effektivwertzeiger = RMS phasor
\[ \begin{gathered} \text{Time domain:} \\[2pt] u_1(t) = u_{L1-N}(t) = 325\,\mathrm{V} \cdot \sin(\omega t) \quad (\varphi_1 = 0) \\[4pt] u_2(t) = u_{L2-N}(t) = 325\,\mathrm{V} \cdot \sin\left(\omega t - \frac{2}{3}\pi\right) \\[4pt] u_3(t) = u_{L3-N}(t) = 325\,\mathrm{V} \cdot \sin\left(\omega t - \frac{4}{3}\pi\right) \\[6pt] \text{Phases:} \\[2pt] \varphi_1 = 0 \\[4pt] \varphi_2 = -\frac{2}{3}\pi = +\frac{4}{3}\pi \\[4pt] \varphi_3 = +\frac{2}{3}\pi = -\frac{4}{3}\pi \end{gathered} \]
Time waveforms of the phase voltages u1(t), u2(t), u3(t) with peak value 325 V
\[ \begin{gathered} \text{RMS phasors:} \\[2pt] U = \frac{\hat{u}}{\sqrt{2}} = 230\,\mathrm{V} \\[4pt] U_1 = 230\,\mathrm{V} \cdot e^{j0} \\[4pt] U_2 = 230\,\mathrm{V} \cdot e^{-j\frac{2}{3}\pi} = 230\,\mathrm{V} \cdot \left(-\frac{1}{2} - j\frac{\sqrt{3}}{2}\right) \\[4pt] U_3 = 230\,\mathrm{V} \cdot e^{j\frac{2}{3}\pi} = 230\,\mathrm{V} \cdot \left(-\frac{1}{2} + j\frac{\sqrt{3}}{2}\right) \\[6pt] U_1 + U_2 + U_3 = 230\,\mathrm{V} + 230\,\mathrm{V}\left(-\frac{1}{2} - j\frac{\sqrt{3}}{2}\right) + 230\,\mathrm{V}\left(-\frac{1}{2} + j\frac{\sqrt{3}}{2}\right) = 0\,\mathrm{V} \end{gathered} \]

In a three-phase voltage system, three voltage sources are connected in star. In the figure above, these are the sources U1, U2 and U3. This time the star point has been moved to the centre of the figure. The sources all have the RMS value U = 230V. This voltage acts between the terminals LX and N. In the grid (e.g. in your home), conductor N always has the electrical potential 0V. It is the electrical ground of the system.

The directions of the voltage arrows at the sources on the left of the figure correspond to the directions of the voltage vectors in the phasor diagram on the right. The three voltage sources are drawn graphically rotated by 120° relative to one another. This does not mean that they have to be arranged like this in reality. It only corresponds to the rotation of the complex phasors of the voltages. This indicates the phase shift of the voltages relative to one another in the circuit diagram.

A three-phase voltage system generally has 5 terminals. One terminal is at earth potential; it normally carries no current and is present only for safety reasons (PE). This terminal is rarely drawn in electrical circuit diagrams. I have left it out. You can see the other 4 terminals in the figure above. There is one terminal in the middle (N) and three terminals on the outside (L1 to L3). The letter L here stands for “line” (German: Leitung), not for inductance as in electrical engineering. So L denotes a connection point or a conductor to which something can be connected. A connection point is, for example, one of the contacts in a socket.

The letters U, V and W are often used for L1 to L3:

\[ \begin{gathered} U\text{: } L_1 \\[4pt] V\text{: } L_2 \\[4pt] W\text{: } L_3 \end{gathered} \]

A household socket has three terminals. One is the safety terminal PE, which has no function for the energy supply and is therefore left out in the sketch. The other two terminals are N and one of the three terminals LX. A socket is always installed between the N conductor and one of the three L conductors.

In the grid, the grid voltage is specified by the power plant. The current depends on which consumers are connected. It depends on the impedance of the consumers. That is why the voltage is always specified in the grid in the form of sources. The RMS value and phase of the voltage are always constant. The current at a consumer depends on the load. When current and voltage are present at the same time, electrical power acts in consumers.

Download course as PDF

The PDF contains all pages of the course. Interactive content is only available on the website.